It is used as a control cable in elevators, as a power cable in cranes and submersible pumps, to ensure integrity in electrical panels and to prevent complexity.
Nominal Voltage : 450/750 V
Test Voltage : 2750 V
Conductor Type : Pure Copper
Conductor Class: Class 5
Insulation and Coating: Special Izay Mix.
3 Cores: Numeric Code
Orange / Optional
Operating Temp.: 70 °C
Short Circuit Temp.: 250 °C









Send WhatsApp Message
Make A Phone Call
Send E-mail
| NUMBER AND CROSS- SECTIONAL AREA OF CONDUCTOR | MAX. CONDUCTOR RESISTANCE AT TEMPERATURE 20°C | NOMINAL THICKNESS OF INSULATION | NOMINAL THICKNESS OF SHEATH | APPROXIMATE OVERALL DIAMETER | APP. NET
WEIGHT OF
CABLES | CURRENT CARRYING CAPACITY AIR (30°C) |
|---|---|---|---|---|---|---|
| nxmm² | ohm.km | mm | mm | mm | kg/km | A |
| 3X1,5 ECO FLAT | 13,30 | 1,05 | 10,50 | 3,50 | 70 | 24 |
| 3X2,5 ECO FLAT | 7,98 | 1,20 | 12,60 | 4,20 | 107 | 32 |
| 3X4 ECO FLAT | 4,95 | 1,40 | 15,90 | 5,30 | 172 | 42 |
| 3X6 ECO FLAT | 3,30 | 1,55 | 18,00 | 6,00 | 236 | 54 |
| 3X10 ECO FLAT | 1,91 | 1,70 | 21,90 | 7,30 | 381 | 73 |
| 3X16 ECO FLAT | 1,21 | 1,80 | 25,50 | 8,50 | 562 | 98 |
| 3X25 ECO FLAT | 0,780 | 2,05 | 31,50 | 10,50 | 862 | 129 |
| 3X35 ECO FLAT | 0,554 | 2,35 | 37,50 | 12,50 | 1187 | 158 |
| 3X50 ECO FLAT | 0,386 | 2,45 | 42,00 | 14,00 | 1620 | 198 |
| 3X70 ECO FLAT | 0,272 | 2,65 | 48,00 | 16,00 | 2260 | 245 |